HVAC/R Engineering Formulas & Solvers
Comprehensive thermodynamic equations, heat transfer relations, psychrometrics, and hydronic formulas reference compiled for field engineers, energy auditors, and plant managers in Pune.
Sensible & Latent Heat Load Equation Solver
Solve Q_s = 1.08 ร CFM ร ฮT and compute airflow tonnage directly.
Master Equations Directory
Sensible Heat Formula (Air)
Calculates heat required to raise or lower dry air temperature without moisture phase change.
Latent Heat Formula (Moisture)
Calculates heat absorbed or released when water vapor condenses on the evaporator coil.
Total Enthalpy Heat Transfer
Total sensible plus latent cooling capacity based on entering and leaving air enthalpy.
Chilled Water Heat Transfer
Standard hydronic formula for chilled water and cooling tower loop heat rejection.
Hydronic Flow Rate Rule of Thumb
Quick sizing equation for primary and secondary chilled water circulating pumps.
Duct Air Velocity
Determines duct air speed. Recommended: 700-900 FPM for residential main ducts; 1000-1500 FPM for commercial.
Fan Law 1 (Airflow vs RPM)
Airflow volume varies directly with fan speed ratio.
Fan Law 3 (Power Consumption vs RPM)
Motor horsepower increases with the cube of speed! A 20% speed boost requires 73% more electrical power.
Suction Line Superheat
Indicates TXV metering valve operation. Target: 8ยฐF to 14ยฐF at compressor service valve.
Liquid Line Subcooling
Indicates refrigerant charge amount. Target: 10ยฐF to 15ยฐF on TXV systems.
Compression Ratio (CR)
Ratio of head pressure to suction pressure. High ratios (> 4.5) overheat compressor oil and cause valve failure.
Coefficient of Performance to EER
Direct conversion between thermodynamic COP and laboratory rating EER.
Chiller Specific Consumption (IKW/TR)
Primary energy metric for central water-cooled and air-cooled chillers in India. Target: < 0.65 for water-cooled.
Cooling Tower Approach
Measures cooling tower heat rejection efficiency. Typical good performance is within 3ยฐC to 5ยฐC of wet bulb.