R-410A is the commercial standard refrigerant for VRF, packaged units, and high-efficiency splits across Pune. Operates at approximately 60% higher pressures than older R-22 circuits.
R-32 / R-125 (50% / 50%)
A1 (Non-Toxic, Non-Flammable)
GWP: 2088
ODP: 0
R-410A
R-410A is the commercial standard refrigerant for VRF, packaged units, and high-efficiency splits across Pune. Operates at approximately 60% higher pressures than older R-22 circuits.
Antoine Saturation Engine
R-410A PT Saturation Calculator
Compute exact vapor saturation pressure from evaporating/condensing temperature in real-time.
A=4.288 | B=934.3 | C=253.5
Absolute Pressure
-- bar
Gauge Pressure (Manifold)
-- PSI(g)
Atmospheric Saturation
-- kPa
Thermodynamic & Chemical Specifications
Chemical Formula
R-32 / R-125 (50% / 50%)
ASHRAE Flammability
A1 (Non-Toxic, Non-Flammable)
GWP (100-Year)
2088
Compatible Lubricant
Polyolester (POE) Oil
Operating Range (Pune Summer)
Low: 110-135 PSI | High: 350-425 PSI
Retrofit Substitute
Not suitable for R-22 retrofit due to 60% higher operating pressures.
โก Field Charging & Handling Protocols
- Near-azeotropic blend: MUST charge as LIQUID from the cylinder liquid valve.
- Vapor charging will cause fractionation and degrade thermal capacity.
๐ Leak Detection Protocols
- Electronic heated diode or infrared detectors
- Nitrogen pressure holding test at 400 PSI
โป๏ธ Recovery & Legal Compliance
- Recover into DOT-4BA high-pressure cylinders rated for minimum 400 PSI working pressure.
๐ข Target Systems & Applications
โ Commercial VRF / VRV multi-splits
โ Residential inverter split air conditioners
โ High-capacity chilled water fan coil units