R-134a is the global benchmark refrigerant for domestic refrigerators, automotive air conditioners, and large industrial centrifugal chiller plants.
CH2FCF3
A1 (Non-Toxic, Non-Flammable)
GWP: 1430
ODP: 0
R-134a (HFC-134a)
R-134a is the global benchmark refrigerant for domestic refrigerators, automotive air conditioners, and large industrial centrifugal chiller plants.
Antoine Saturation Engine
R-134a (HFC-134a) PT Saturation Calculator
Compute exact vapor saturation pressure from evaporating/condensing temperature in real-time.
A=4.088 | B=898.3 | C=243.6
Absolute Pressure
-- bar
Gauge Pressure (Manifold)
-- PSI(g)
Atmospheric Saturation
-- kPa
Thermodynamic & Chemical Specifications
Chemical Formula
CH2FCF3
ASHRAE Flammability
A1 (Non-Toxic, Non-Flammable)
GWP (100-Year)
1430
Compatible Lubricant
Polyolester (POE) or PAG (Automotive)
Operating Range (Pune Summer)
Low: 15-35 PSI | High: 150-200 PSI
Retrofit Substitute
R-1234yf for automotive or R-513A for commercial chillers.
โก Field Charging & Handling Protocols
- Single-component pure HFC: can be charged as vapor or liquid.
- Ensure strict deep vacuum <500 microns due to extreme POE oil hygroscopic affinity.
๐ Leak Detection Protocols
- Halogen diode detectors, UV dye injection, and bubble test
โป๏ธ Recovery & Legal Compliance
- Standard HFC recovery equipment into clean R-134a cylinders.
๐ข Target Systems & Applications
โ Domestic & commercial refrigerators
โ Automotive vehicle air conditioning
โ Centrifugal and screw water chillers